General Information
-
- Global Commercial Alias:
- PSR12-600-70
-
- Extended Product Type:
- PSR12-600-70
-
- Product ID:
- 1SFA896106R7000
-
- ABB Type Designation:
- PSR12-600-70
-
- EAN:
- 7320500338247
-
- Catalog Description:
- PSR12-600-70 Softstarter
-
- Long Description:
- Softstarter PSR12-600-70 for max 600V main voltage and 100-240V 50/60Hz control supply voltage
Categories
- Products » Drives » Softstarters » Softstarters » PSR Softstarters » PSR12
- Products » Low Voltage Products and Systems » Control Products » Softstarters » Softstarters » PSR Softstarters » PSR12
Dimensions
-
- Product Net Width:
- 114 mm
-
- Product Net Height:
- 140 mm
-
- Product Net Depth / Length:
- 45 mm
-
- Product Net Weight:
- 0.4 kg
Technical
-
- Rated Operational Voltage:
- 208 … 600 V AC
-
- Rated Control Supply Voltage (Us):
- 100 … 240 V AC
-
- Rated Control Circuit Voltage (Uc):
- 50 Hz / 60 Hz 100 … 240 V AC
-
- Rated Frequency (f):
- Main Circuit 50/60 Hz
Control Supply 50/60 Hz
-
- Rated Operational Power – In-Line Connection (Pe):
- (230 V) 3 kW
(400 V) 5.5 kW
(500 V) 5.5 kW
-
- Rated Operational Current – In-Line Connection (Ie):
- 12 A
-
- Service Factor Percentage:
- 100 %
-
- Overload Protection:
- Recommended MS132 10.00 … 16.00
-
- Integrated Electronic Overload:
- No
-
- Adjustable Rated Motor Current Ie:
- No %
-
- Starting Capacity at Maximum Rated Current Ie:
- 4xIe for 6s
-
- Ramp Time:
- During Start 1 … 10 second [unit of time]
During Stop 0 … 20 second [unit of time]
-
- Initial Voltage During Start:
- 40 … 70 %
-
- Step Down Voltage Special Ramp:
- 100 … 60 %
-
- Current Limit Function:
- No
-
- Switch for Inside Delta Connection:
- No
-
- Run Signal Relay:
- Yes
-
- By-pass Signal Relay:
- No
-
- Fault Signal Relay:
- No
-
- Overload Signal Relay:
- No
-
- Signal indication completed start ramp (LED):
- Green
-
- Signal indication ready to start/standby ON (LED):
- Green
-
- Signal indication running R (LED):
- Green
-
- Signal indication ramping up/down (LED):
- Green
-
- Number of Starts Per Hour at 3.5*Ie for 7 sec. 50% ON Time 50% OFF Time:
- 10
-
- Communication:
- FiledBusPlug(Optional)
-
- Degree of Protection:
- acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP20
-
- Terminal Type:
- Screw Terminals
-
- Connecting Capacity Main Circuit:
- Rigid 1/2×0.75 … 2.5 mm²
-
- Connecting Capacity Control Circuit:
- Rigid 1/2 x 0.75 … 2.5 mm²
-
- Connecting Capacity Supply Circuit:
- Rigid 1/2×0.75 … 2.5 mm²
-
- Tightening Torque:
- Main Circuit 1 N·m
Supply Circuit 1 N·m
Control Circuit 1 N·m
-
- Product Main Type:
- PSR12
Reviews