General Information
-
- Extended Product Type:
- UA95-30-00-80
-
- Product ID:
- 1SFL431022R8000
-
- EAN:
- 7320500144572
-
- Catalog Description:
- UA95-30-00 220-230V 50Hz / 230-240V 60Hz Contactor
-
- Long Description:
- A 3-phase Contactor suitable for Capacitor switching application. Maximum permissible peak current 30 times the nominal RMS current. Operated with a control voltage, versions from 24…….690 V
Dimensions
-
- Product Net Width:
- 90 mm
-
- Product Net Depth / Length:
- 123.5 mm
-
- Product Net Height:
- 148 mm
-
- Product Net Weight:
- 1.8 kg
Technical
-
- Number of Main Contacts NO:
- 3
-
- Number of Main Contacts NC:
- 0
-
- Number of Auxiliary Contacts NO:
- 0
-
- Number of Auxiliary Contacts NC:
- 0
-
- Rated Operational Voltage:
- Main Circuit 1000 V
-
- Rated Frequency (f):
- Main Circuit 50/60 Hz
-
- Conventional Free-air Thermal Current (Ith):
- acc. to IEC 60947-4-1, Open Contactors q = 40 °C 145 A
-
- Rated Operational Power AC-3 (Pe):
- (380 / 400 V) 45 kW
-
- Rated Operational Power AC-6b (Pe):
- (230 / 240 V) 40 °C, 50 / 60 Hz 35 kvar
(230 / 240 V) 55 °C, 50 / 60 Hz 35 kvar
(230 / 240 V) 70 °C, 50 / 60 Hz 30 kvar
(400 / 415 V) 40 °C, 50 / 60 Hz 65 kvar
(400 / 415 V) 70 °C, 50 / 60 Hz 55 kvar
(400 / 415 V) 55 °C, 50 / 60 Hz 65 kvar
(440 V) 40 °C, 50 / 60 Hz 65 kvar
(440 V) 55 °C, 50 / 60 Hz 65 kvar
(440 V) 70 °C, 50 / 60 Hz 55 kvar
(500 / 550 V), 40 °C, 50 / 60 Hz 70 kvar
(500 / 550 V) 55 °C, 50 / 60 Hz 70 kvar
(500 / 550 V) 70 °C, 50 / 60 Hz 60 kvar
(690 V) 40 °C, 50 / 60 Hz 80 kvar
(690 V) 55 °C, 50 / 60 Hz 80 kvar
(690 V) 70 °C, 50 / 60 Hz 70 kvar
-
- Rated Short-time Withstand Current (Icw):
- at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 800 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 160 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 350 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1320 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 500 A
-
- Maximum Breaking Capacity:
- cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 1160 A
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 800 A
-
- Maximum Electrical Switching Frequency:
- 240 cycles per hour
-
- Rated Insulation Voltage (Ui):
- acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V
acc. to UL/CSA 600 V
-
- Rated Impulse Withstand Voltage (Uimp):
- Main Circuit 8 kV
-
- Mechanical Durability:
- 10 million
-
- Maximum Mechanical Switching Frequency:
- 3600 cycles per hour
-
- Coil Operating Limits:
- (acc. to IEC 60947-4-1) 0.85 x Uc Min. … 1.1 x Uc Max. (at θ ≤ 70 °C)
-
- Rated Control Circuit Voltage (Uc):
- 50 Hz 220 … 230 V
60 Hz 230 … 240 V
-
- Coil Consumption:
- Holding at Max. Rated Control Circuit Voltage 50 Hz 22 V·A
Holding at Max. Rated Control Circuit Voltage 60 Hz 26 V·A
Pull-in at Max. Rated Control Circuit Voltage 50 Hz 350 V·A
Pull-in at Max. Rated Control Circuit Voltage 60 Hz 450 V·A
-
- Operate Time:
- Between Coil De-energization and NC Contact Closing 7 … 15 ms
Between Coil Energization and NO Contact Closing 10 … 25 ms
-
- Connecting Capacity Main Circuit:
- Bar 30 mm²
Flexible with Cable End 2 x 6 … 35 mm²
Rigid 1 x 10 … 95 mm²
-
- Connecting Capacity Auxiliary Circuit:
- Flexible with Ferrule 2x 0.75 … 2.5 mm²
Flexible with Insulated Ferrule 2x 0.75 … 2.5 mm²
Flexible 2×0.75 … 2.5 mm²
Solid 2 x 1 … 4 mm²
Stranded 1 x 1 …. 4 mm²
-
- Degree of Protection:
- acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20
acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP10
-
- Connecting Terminals (delivered in open position) Main Poles:
- M8 hexagon socket screw with single connector
-
- Terminal Type:
- Cable Clamp
Technical UL/CSA
-
- Maximum Operating Voltage UL/CSA:
- Main Circuit 600 V
-
Reviews
There are no reviews yet.