| range of product |
Zelio Time
|
|
|---|---|---|
| product or component type |
Modular timing relay
|
|
| discrete output type |
Relay
|
|
| width |
17.5 mm
|
|
| device short name |
RE17R
|
|
| time delay type |
At
Di Ht H C Ac A D B Bw |
|
| time delay range |
1…10 h
0.1…1 s 6…60 s 10…100 h 6…60 min 1…10 s 1…10 min |
|
| nominal output current |
8 A
|
| contacts type and composition |
1 C/O
|
|
|---|---|---|
| contacts material |
Cadmium free
|
|
| height |
90 mm
|
|
| depth |
72 mm
|
|
| control type |
Selector switch front panel
|
|
| [Us] rated supply voltage |
12…240 V AC/DC 50/60 Hz
|
|
| voltage range |
0.85…1.1 Us
|
|
| supply frequency |
50…60 Hz +/- 5 %
|
|
| release of input voltage |
5 V
|
|
| connections – terminals |
Screw terminals, 1 x 0.5…1 x 3.3 mm² (AWG 20…AWG 12) solid without cable end
Screw terminals, 2 x 0.5…2 x 2.5 mm² (AWG 20…AWG 14) solid without cable end Screw terminals, 1 x 0.2…1 x 2.5 mm² (AWG 24…AWG 14) flexible with cable end Screw terminals, 2 x 0.2…2 x 1.5 mm² (AWG 24…AWG 16) flexible with cable end |
|
| tightening torque |
0.6…1 N.m conforming to IEC 60947-1
|
|
| housing material |
Self-extinguishing
|
|
| repeat accuracy |
+/- 0.5 % conforming to IEC 61812-1
|
|
| temperature drift |
+/- 0.05 %/°C
|
|
| voltage drift |
+/- 0.2 %/V
|
|
| setting accuracy of time delay |
+/- 10 % of full scale at 25 °C conforming to IEC 61812-1
|
|
| control signal pulse width |
100 ms with load in parallel typical
30 ms typical |
|
| insulation resistance |
100 MOhm at 500 V DC conforming to IEC 60664-1
|
|
| reset time |
120 ms on de-energisation typical
|
|
| on-load factor |
100 %
|
|
| power consumption in VA |
0…3 VA at 240 V AC
|
|
| maximum power consumption in W |
1.5 W at 240 V DC
|
|
| minimum switching current |
10 mA at 5 V DC
|
|
| maximum switching current |
8 A AC/DC
|
|
| maximum switching voltage |
250 V AC
|
|
| breaking capacity |
2000 VA
|
|
| operating frequency |
10 Hz
|
|
| electrical durability |
100000 cycles (8 A at 250 V AC maximum) for resistive load
|
|
| mechanical durability |
10000000 cycles
|
|
| dielectric strength |
2.5 kV 1 mA/1 minute 50 Hz conforming to IEC 61812-1
|
|
| [Uimp] rated impulse withstand voltage |
5 kV during 1.2/50 µs
|
|
| power on delay |
100 ms
|
|
| marking |
CE
|
|
| creepage distance |
4 kV/3 conforming to IEC 60664-1
|
|
| safety reliability data |
MTTFd = 296.8 years
B10d = 270000 |
|
| mounting position |
Any position in relation to normal vertical mounting plane
|
|
| mounting support |
35 mm DIN rail conforming to EN/IEC 60715
|
|
| local signalling |
LED indicator for on steady: relay energised, no timing in progress
LED indicator for flashing: timing in progress 80 % ON and 20 % OFF LED indicator for pulsing: relay de-energised, no timing in progress (except function Di-D, Li-L) 5 % ON and 95 % OFF |
|
| net weight |
0.07 kg
|
|
| time delay type |
A, Ac, At, B, Bw, C, D, Di, H, Ht
|
|
| functionality |
Multifunction
|
|
| compatibility code |
RE17
|